Description
3 watt/foot, 120 volt, self-regulating, heater cable with tinned copper braid and polyolefin overjacket for wet applications
Service Voltage: 120
Maximum Segment Length: 221'
Maximum Maintain Temperature: 150°F
Maximum Intermittent Exposure: 185°F
Maximum Length on Circuit Breaker:
Start-Up Temperature |
15A |
20A |
30A |
---|---|---|---|
50°F |
221' |
n/a |
n/a |
0°F |
208' |
221' |
n/a |
-20°F |
187' |
221' |
n/a |
Approvals/Classifications:
UL for Ordinary Locations
CSA for Ordinary Locations